SMARD series dryers - Static condenser with +3ºC dew point

See the choice of models
+ -
Water (Vapor)
Dew point +3°C
Classe iso : 4
9876543210

Performant and silent


...with a concept developed specifically for the SMARD SC series.

The static condenser doesn’t need a ventilator and thus functions very silently and is not prone to issues because of dust.

Furthermore, the condenser isn’t sensitive to ambient temperature variations and needs no application of correction factors.

Thanks to a constant pressure regulation valve the dew point is stabilised at +3ºC.

The range comprises 4 models covering flow rates up to 100m3/hr under 7 bar pressure.

All models are exchange-guaranteed for 2 years.


    •    ISO 8573-1:2001 = 4 class +3ºC pressure dew point 

    •    double-effect static condenser included in the body

    •    insensible to ambient temperature variations

    •    very silent

    •    constant pressure expansion valve

    •    non-pollutant refrigerant

    •    analog display of the dew point

    •    condensate drain with temporised solenoid valve

    •    low power consumption

    •    low clutter

    •    exchange-guarantee for 2 years


Model
     
Model Input connection Flowrate (m³/h) My wish
SC 5 3/8” 20
SC 10 3/8” 30
SC 18 3/4” 60
SC 24 3/4” 80
SC 30 3/4” 100
Advise me    

* Select the generic if you don't know which model to choose. The sales department will contact you to determine the appropriate model.

The SMARD SC dryers are equipped with a double-condenser technology.

The condenser is used not only to dispose of the ambient air compression calories, but also to heat the cold compressed air coming out of the evaporator.

The condensation capacity is thus superior and totally independent of the ambient temperature.

Furthermore, the static condenser doesn’t need a ventilator and thus functions very silently, allowing an implementation near the location of use without causing inconvenience to staff.

The reliability of the dew point is guaranteed by a constant pressure regulation valve offering optimal efficiency of the cooling circuit for 0 to 100% of the flow treated.

A solenoid valve disposes  of condensed water.

Detailed specifications

Common data

Fluid to dry

Compressed air
Bodywork Steel, b/w epoxy paint

Inlet/Outlet Rear side

Refrigerant

R 134 A
Installation Indoor, frost-protected

Condensate drain

Temporised solenoid valve

Electric power

240 V / 1 Ph / 50 Hz
Protection IP 44
Garantee 2 year exchange-guarantee (drain excl.)

Correction factor

Any deviation of the nominal parameters causes the use of the following correction factors.

F1- Correction factor depending on operating pressure

Pressure (B) 3 4 5 6 7 8 9 10 11 12 13 14
Factor (F1) 0.79 0.87 0.92 0.96 1.00 1.03 1.07 1.10 1.13 1.16 1.18 1.21

F2- Correction factor depending on inlet air temperature

Temp. (°C) 35 40 45 50 55
Factor (F2) 1 0,84 0,71 0,63 0,55

Correction factor depending on ambient temp.
none